| Sign In | Join Free | My carsrow.com | 
              
  | 
      
Brand Name : Fanke High-Voltage
Model Number : FKJB
Certification : ISO9001
Place of Origin : China
MOQ : One unit
Price : Negotiable
Payment Terms : T/T
Supply Ability : 10units/month
Delivery Time : 15-20work days
Packaging Details : Export standard wooden case with fumigation free
Usage : All knids of Relays calibration testing
Output : 4U3I channels output
Current source : 3*30A
Voltage source : 4*120V
Test Accuracy : no less than 0.2%
Output frequency : 0~1000Hz
Protection Relay Test Set , 4U3I Relay Analyzer , Relay Calibration Tester , Relay Protector Comprehensive Tester
 
I. Technical Description
 
 
 
II. Function and features
III. Technical index:
1.AC current source
| Max.current output | 3×30A/phase | Resolution | 1 mA | 
| 90A/ 3-ph in parallel | Voltage rise and fall time | ≤200µS | |
| Max. power output | 
			 450 VA/phase, 900 VA/3-ph in parallel  | 
			Amplitude-frequency characteristic | 
			 Amplitude of variation ≤±0.5% within 25~1000 Hz  | 
		
| Output current, amplitude, frequency, and phase of each phase | Adjustable independently | Time of output | 
			 Continuous output within 0~10A; Continuous time is more than 60S within 10A~20A; Continuous time is more than 10S within >20A  | 
		
| Output accuracy | ±0.2%±0.02% of full range within 0.2A~30A | 
2.AC voltage source
| Max. voltage output | 4×120V/phase | Resolution | 1 mV | 
| Max. power of output voltage | 60 VA/phase | Voltage rise and fall time | ≤120µS | 
| Output amplitude, frequency, and phase of each phase | Adjustable independently | Amplitude-frequency characteristic | Amplitude of variation≤±0.5% within 25~1000 Hz | 
| Output accuracy | 
			 ±0.1%±0.02% Of full range within 2~120V  | 
			||
3.DC voltage source
| Voltage output | 0~300V(±150V) | Resolution | 1 mV | 
| Accuracy | 0.5% | Max. power output | 100 VA | 
4.Auxiliary DC source
| Voltage range | 110V or 80%~100% of 220V | 110V or 220V adjustable DC power output | 
| Max. power output | 100 VA | 
5.Phase angle
| Range | 0°~360° | Resolution | 1° | 
| Accuracy | ±1° | 
6.Frequency
| Range | 25~1000 Hz | Synchronism | ≤10μS | 
| Accuracy | 
			 At 25~65 Hz, absolute deviation≤0.001 Hz; At 65~450 Hz, absolute deviation≤0.01 Hz; At 450~1000 Hz, absolute deviation≤0.1 Hz  | 
			Superposition any harmonic from two to nine. | |
7.Input
| Input impedance | ≥10KΩ | Timing precision | ≤1 mS when less than 1S | 
| Resolution | 0.1 mS | Connection point | 
			 When input voltage is within 0~±5V, it is shorted; When input voltage is within +15V~+250V or -15V~-250V, the idle contact is open.  | 
		
| 8-independent switch contact input | |||
8.GPS trigger
| Capacitance | 
			 250V DC,0.5A; 250V AC,0.5A  | 
			GPS trigger | error:≤50μS | 
| 4 pairs of programmable switching contact output | |||
9.Power source
| AC voltage input | 
			 Rated value: 220V-20%~+15%; Reference value: 220V±2%  | 
			AC power frequency | 
			 Rated value: 50 Hz-4%~+2%; Reference value: 50 Hz±1%  | 
		
| Input power | 
			 ≤1000 VA;(≥10S) ≤2000 VA : for short time  | 
		
10.Dimensions and using conditions
| Dimensions | 
			 390×190×360 (W×H×D;mm)  | 
			Using conditions | 
			 T:-5~+45℃ RH:≤90% Atmospheric pressure:80~110 kPa  | 
		
| Weight | About 19 kg | 
 
V.Working conditions
| 
                                             | 
                
                        4U3I Channels Output Relay Test Set / Relay Test Kit High Accuracy 0~1000Hz Images |